The TRICONEX TRICON system is the core of Triple Modular Redundancy (TMR) Safety Instrumented Systems (SIS), widely used in high-risk industries such as petrochemicals, natural gas, power, and pharmaceuticals to ensure the safety control of critical processes. Its modular design supports high reliability, online maintenance, and fault tolerance.
![]()
1. Main Processor Module
Model: 3008/3009/3101
Function:
-Implement security logic control, using 3 independent processors running in parallel , and ensuring security through a 2-out-of-3 (2oo3) voting mechanism.
-Support online modification of logic and hot swappable replacement (requiring redundant configuration).
key parameter
-Processor architecture: PowerPC/x86 (different models)
-Scanning cycle *: 10ms~2s (configurable)
-Memory: 16MB~512MB (depending on model)
-Communication interface:
-Support TriStation 1131 * * programming software
-Supports Modbus TCP/IP, OPC UA, Ethernet/IP
-Safety level: SIL 3 (IEC 61508)**
-Working temperature: -40 ° C~+70 ° C
—
2. Digital Input Module (DI)
Model: 3700A/3704E (32 channels)
Function:
-Collect on-site switch signals (such as emergency stop buttons, liquid level switches, pressure switches, etc.).
-Supports NAMUR sensor input (applicable to hazardous areas).
Key parameters:
-Input type: dry contact/24VDC/NAMUR
-Number of channels: 8/16/32 (different models)
-Response time:<5ms
-Isolation voltage: 1500VAC (between channels)
-Diagnostic function: open circuit and short circuit detection
-Safety certification: SIL 3
### **3. Analog Input Module (AI)**
####Model: 3503E/3504E (16 channels)**
**Function * *:
-Collect analog signals such as 4-20mA, 0-10V, etc. (such as temperature, pressure, flow transmitters).
-Supports * * HART communication * * (requires cooperation with a HART modulator).
**Key parameters * *:
-* * Input range * *: 4-20mA/0-10V/RTD/TC (thermocouple)
-* * Resolution * *: 16 bits (0.05% accuracy)
-Isolation between channels: 250VAC
-* * Sampling rate * *: 50ms/channel
-* * Diagnostic function * *: Over limit and wire breakage detection
-* * Safety level * *: * * SIL 3**
—
### **4. Digital Output Module (DO)**
####Model: 3805E/3806E (8 channels)**
**Function * *:
-Control switch devices such as relays and solenoid valves.
-Support * * short circuit protection * * and * * fail safe status * *.
**Key parameters * *:
-Output Type: Relay/Transistor (24VDC)
-* * Load capacity * *: 2A/channel (relay)
-* * Response time * *:<10ms
-Isolation voltage: 1500VAC
-* * Safe mode * *: * * De energize on Fault (power off in case of failure)**
-* * Certification * *: * * SIL 3**
—
### **5. Communication Modules**
####Model: 4351B (Modbus TCP/IP)/4329 (Ethernet/IP)**
**Function * *:
-Communicate with DCS, PLC, SCADA systems.
-Support * * redundant communication * * (dual network ports).
**Key parameters * *:
-* * Protocol support * *: Modbus TCP/IP, OPC UA, Ethernet/IP
-* * Communication speed * *: 10/100/1000 Mbps
-* * Maximum number of connections * *: 32 (Modbus TCP)
-* * Security Features * *: Data Verification, CRC Error Detection
—
##* * Typical application cases**
###Case 1: Emergency Shutdown System (ESD) for Offshore Oil Platforms**
-* * System Configuration * *:
-* * Main processor * *: TRICON 3008 (TMR)
-* * DI module * *: 3704E (collecting ESD button, flame detector)
-DO module: 3805E (control shut-off valve)
-Communication module: 4351B (integrated with DCS)
-* * Effect * *:
-Fault detection time<100ms
-Prevent accidental parking (2oo3 voting mechanism)
-Compliant with SIL 3 * safety standards.
Case 2: Chemical Plant Combustion Management System (BMS)**
-System configuration * *:
-Main processor: TRICON 3101
-AI module: 3503E (monitoring furnace temperature and gas pressure)
-DO module * *: 3806E (controlling fuel valve)
-Effect:
-Prevent burner explosion (automatic shutdown due to overheating)
-Support online maintenance to reduce downtime.
—
The card module of the TRICONEX system has core advantages such as high reliability, TMR redundancy, and SIL 3 certification, making it suitable for critical safety control. The main modules include:
1. * * Main processor (3008/3101) * * – executes security logic
2. * * Digital input (3704E) * * – Collect switch signals
3. * * Analog Input (3503E) * * – Monitoring Process Variables
4. * * Digital output (3805E) * * – Control actuator
5. * * Communication module (4351B) * * – Integrated with upper level system
These modules together form a complete Safety Instrumented System (SIS) to ensure the safe operation of industrial processes.